Jadual Pemilihan Peranti Perlindungan Litar

Distribution Board

Jadual Pemilihan Peranti Perlindungan Litar ini panduan asas untuk Rekabentuk Litar Kecil Akhir (Final Sub Circuit) di Kotak Agihan (Distribution Board).

This Schedule Of Circuit Protective Device Selection is a basic guideline for Final Sub Circuit Design at Distribution Board.

 

JADUAL PEMILIHAN PERANTI PERLINDUNGAN LITAR
(SCHEDULE OF CIRCUIT PROTECTIVE DEVICE SELECTION)
Bil. Jenis Litar Kecil Akhir Fasa Peranti Perlindungan Litar
(Circuit Protective Device)
(Type Of Final Sub-Circuit) (Phase) ELCB/RCD/RCCB
Amp Pole (Sensivity Value)
1.0 Lampu 1 40A DP 100mA
(Lighting) 3 63A TPN 100mA
bercampur atau berasingan
(mixed or separate)
2.0 Pendingin Hawa 1 40A DP 100mA
(Air Conditioning) 3 63A TPN 100mA
3.0 Motor Elektrik 1 40A DP 100mA
(Electric Motor) 3 63A TPN 100mA
4.0 13A/15A Soket Alir Keluar 1 40A DP 30mA
(13A/15A Switch Socket Outlet) 3 63A TPN 30mA
5.0 Pemanas Air 1 20A DP 10mA
(Water Heater)
 Nota
ELCB Earth Leakage Circuit Breaker
RCD  Residual Current Device
 RCCB  Residual Current Circuit Breaker
 DP Double Pole
 TPN Three Pole & Neutral

 